Appendix A Hayes Commands
Page 57 © January 2011
Enable CRC Error Checking
Restore Factory Defaults. This function is also available from the DIP Switches.
Set module’s Group Address Range 0-255. Default 0.
Flow Control Configuration.
Flow Control Disabled. CTS Always high. Module ignores RTS.
CTS/RTS Flow Control. CTS Reflects the state of the local buffer. Module only
transmits serial data when RTS is high.
RS-485 Control. Must be selected for RS-485 to work. CTS is high. CTS goes
low when transmitting data. RTS is ignored.
AT&L Configuration of start-up mode, and controlled mode operation.
&L0 At power-up, the module enters command mode and waits for commands.
Normal single-connect controlled mode operation.
&L1•
If set to transparent mode in AT&M, the module automatically goes online. For
controlled mode, ATD automatically dials the number stored in Z0, ATA answers
an incoming call.
&L2 Auto-connect mode - master. The module “dials” the number stored in &Z0
automatically. It continuously attempts to connect to that number. Use DTR with
the AT&D command to control the connection.
Auto-connect mode - slave. The module continuously attempts to answer any
incoming call. Use DTR with the AT&D command to control the connection.
Operating Mode. This allows selection between transparent mode, controlled
mode and fast operation mode.
&M0•
Transparent Repeater. All serial data is sent out the radio, with the configured
system (AT&S) and group (AT&G) address. All incoming radio data with the
correct system address and matching group address is sent out the serial port, and
also re-transmitted out the radio port using the unit address (AT&U) setting as the
group address. All incoming radio data with the configured system address and
group address matching the Unit address is re-transmitted out the radio with the
group address set to the group address.
Fast Operation Controlled Mode. No repeaters may be used.
Abort Connection Control. Controls whether the module will abort a connection
attempt in controlled mode if a character is entered.
Ignore characters entered while attempting to make a connection.