Man_905D_1.10.doc Page 46
Set the serial data rate to 38400 ATC6
Set the radio data rate to 19200 not necessary (default)
Set the character type to 7,1,2,even AT&B13
Exit and save the configuration AT&W ATO
The operating mode will already be in transparent mode from the factory default settings. The
other default values for the other parameters will likely be OK.
Repeater Configuration
Set the module to factory default settings: AT&F
Set the system address to the same random number: AT&S138
Set the group address and unit (secondary group) address AT&G1 AT&U2
The group address for the right hand side module will be set to 2 (this corresponds to the
secondary address of the repeater).
Note that the repeater will only output data to its PLC for messages received from the first 905U-D. It
will not output data from the right-hand PLC. If you set both group addresses to 1, then the repeater will
output data from both sides - this is only possible when there is only one repeater. The disadvantage of
this is that both sides will hear the re-transmitted message - that is, the PLC that sent the message will
receive the same message back as a re-transmitted message. This is not a problem with most PLC’s, but
is with a small number of brands. For these brands, use a different group address either side of the
repeater.
Set the serial data rate to 9600 ATC4
Set the radio data rate to 19200 not necessary (default)
Set the character type to 7,1,2,even AT&B13
Set the operating mode to Transparent Repeater AT&M1&L1
Exit and save the configuration AT&W ATO
Right-hand Unit Configuration
Set the system address to the same random number: AT&S138
Set the group address AT&G2
Set the serial data rate to 9600 ATC4
Set the radio data rate to 19200 not necessary (default)
Set the character type to 7,1,2,even AT&B13
Exit and save the configuration AT&W ATO